CREARD

Creard R-407H

Low GWP, Low Cost service solution for R-404A/507 in MT and LT applications.

Creard R-407H

A low GWP and Low Cost service solution for R-404A/507 in MT and LT applications

The European F-Gas regulation EU517/2014 is upon us. Effective since 2015, the regulation is entering a new phase of accelerated phasedown of the HFC consumption within the EU28. Compared to the baseline year of 2015, a reduction step of 37% of available quota is set for January 2018. Even in 2017, the requirement that imported pre-charged equipment consumes quota will add pressure on available quota. Owners and operators of existing installations need to find urgently cost effective solutions to maintain their equipment and cooling service.

Who is at risk?

Industry studies have shown that the largest burden on the F-gas industry to reduce its CO2 footprint will be carried by the commercial refrigeration sector. Especially impacted are systems running on high GWP refrigerants such as R-404A / R-507. According to EPEE’s Gapometer study, 50% of existing R-404A systems should be replaced or converted to a lower GWP refrigerant by January 2018 to meet this requirement.

This raises a huge challenge for our industry. Indeed, the race to retrofit these high GWP gases in commercial systems puts even more short-term pressure on quota availability. This fact, combined with further step-downs in F-gas quota means that the right choice of refrigerant is critical for initial retrofit and future service.

Choosing a Low GWP and Low Cost retrofit refrigerant – a 3-component choice

The F-gas cap and phasedown schedule for CO2 equivalent quota will inevitably put increasing pricing pressure on each tonne of CO2 required by the EU market. It is therefore essential that plant owners and operators get to the lowest GWP levels for an A1 refrigerant in their commercial refrigeration installations. Any refrigerant with a GWP greater than 1500 will see rapidly increasing cost pressure and may even require a second retrofit to lower GWPs in order to meet the cap and phasedown schedule.

Creard R-407H is an A1 classified refrigerant with a GWP <1500

R-407H is a mixture of R32 / R125 / R134a. It has been specially developed to enable a low-cost conversion of R-404A and R-507 systems without the need for expensive HFO components.
We at DAIKIN believe that the EU refrigeration industry will need HFO based solutions to comply with the F-gas regulation. Indeed, DAIKIN has a broad portfolio of HFO technologies. However, it is a fact that HFO molecules are more expensive to produce than traditional HFCs. We believe that the industry should only pay for HFOs or even more expensive solutions when absolutely necessary. For the replacement of most R-404A / R-507 MT and LT systems, Creard R407H provides equivalent performance to HFO-based technologies with a GWP also below 1500.

In most cases, Creard R-407H can be used without major changes to existing R-404A / R-507 systems. R-407H can be considered a „drop in“ solution for many systems 2. Studies have shown that R-407H has an improved COP vs other HFO/HFC based replacement refrigerants and better cooling capacity than R-404A.

We believe that multiple solutions will be necessary to meet the F-gas Regulation.
HFO based technologies will be a part of those solutions and DAIKIN’s portfolio reflects these technologies.
However, for many A1 refrigeration applications where replacement of R-404A / R-507 is the greatest challenge for users and contractors, Creard R-407H can meet their F-gas needs by offering:

Lower GWP<1500
Performanceequivalent or higher than R-404A/R-507
Lower costno need for more expensive HFO based blends
Ease of Retrofita drop in solution for many systems

2 However, R-407H cannot be considered a „drop-in“ for every system. For example, due to R-407H’s higher discharge temperature compared to R-404A / R-507, measures such as liquid injection would need to be considered for discharge temperatures exceeding 80°C.

Creard R-407H as replacement for R-22 in US-based cold storage
  • (PDF, English)
Creard R-407H as replacement for R-404A under difficult cycle parameters
  • (PDF, English)
Creard R-407H as replacement for R-404A in cold storage (3°C)
  • (PDF, English)
Creard R-407H as replacement for R-507 in cold storage (-24°C)
  • (PDF, English)

Physical data 3

  R-404AR-507Creard R-407H
Chemical Formula CHF2CF3
CH3CF3
CH2FCF3
CHF2CF3/
CH3CF3
CH2F2
CHF2CF3/
CH2FCF3
Molar Masskg/kmol97.698.86113.07
Boiling Point at 1.013 bar°C-46.2-46.74-44.7
Critical Temperature°C72.070.686.5
Critical Pressurebar37.2937.148.5
liq. cp 4kJ/(kgK)1.5421.5391.585
vap. cp 4kJ/(kgK)1.2211.2251.176
Ratio cp/cv, vap. 4 1.371.381.36
Spec. density, liq. 4kg/m³104410481111
Spec. density, vap. 4kg/m³65.2768.8941.86
Enthalpy of vaporization 4kJ/kg140.26136.45199.02
Explosive limit in air 5% v/vN/AN/AN/A
3 Thermo-physical data calculated by Refprop 9.0
4 sat. @ 25°C
5 T = 25°C, p= 1.013bar

For more Information or any questions you have:

Our Sales or Technical Service staff will be happy to help.

Contact us